30404-10
Circuit Breakers
CIRCUIT BREAKER
30404-10
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.000 minimum at 200 pct all locations and 10.000 maximum at 200 pct all locations
-
Switch Voltage Rating And Type In Volts
250.0 ac and 30.0 dc
-
Maximum Continuous Load Current Rating Per Pole
45.0 amperes ac all locations
-
Actuator Position Designation
at pole two
-
Switch Contact Arrangement
single pole, double throw
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Mounting Facility Type And Quantity
6 threaded hole
-
Unpackaged Unit Weight
9.500 ounces
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Body Width
2.250 inches nominal
-
Mounting Surface To Terminal End Distance
2.720 inches nominal
-
Switch Current Rating And Type In Amps
10.0 ac and 4.0 dc
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Body Length
2.500 inches nominal
-
Boss Height
0.140 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Frequency In Hertz
400.0 all locations
-
Auxiliary Switch Function And Quantity
1 alarm
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Terminal Type And Quantity
6 threaded stud
-
Fragility Factor
moderately rugged
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
130.0 all locations
-
Switch Terminal Type
tab, solder lug
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Reset Method
manual
-
Switch Location And Position Designation
internal at pole three
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type