1211297-202
Circuit Breakers
CIRCUIT BREAKER
1211297-202
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
magnetic single location
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac single location
-
Switch Voltage Rating And Type In Volts
250.0 ac
-
Thread Series Designator
unc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Reset Method
manual
-
Nominal Thread Size
0.500 inches
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one
-
Body Width
0.750 inches nominal
-
Switch Current Rating And Type In Amps
10.0 ac
-
Actuator Function
trip-reset
-
Body Length
2.000 inches nominal
-
Terminal Type And Quantity
2 screw
-
Circuit Protection Type
overcurrent single location
-
Switch Contact Arrangement
single pole, double throw
-
Pole Quantity
1
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
3.000 minimum at 200 pct single location and 20.000 maximum at 200 pct single location
-
Bushing Length
0.625 inches nominal
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac single location
-
Frequency In Hertz
47.5 single location or 63.0 single location
-
Center To Center Distance Between Terminals Parallel To Length
1.530 inches nominal
-
Mounting Surface To Terminal End Distance
2.232 inches maximum
-
Body Style
single pole type
-
Auxiliary Switch Function And Quantity
1 alarm
-
Switch Terminal Type
screw
-
Switch Location And Position Designation
internal at pole one