6510-001-5
Circuit Breakers
CIRCUIT BREAKER
6510-001-5
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
2 threaded stud
-
Trip Release Method
thermal all locations
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac all locations and 5.0 amperes dc all locations
-
Case Material
plastic
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 ac all locations and 28.0 dc all locations
-
Overall Width
2.250 inches maximum
-
Frequency In Hertz
400.0 all locations
-
Inclosure Protection Type For Which Designed
general purpose
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3600.0 ac all locations and 3600.0 dc all locations
-
Pole Quantity
1
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Mounting Facility Type And Quantity
2 threaded hole
-
Internal Trip Release Configuration
series trip all locations
-
Trip Release Characteristic
time delay all locations
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Overall Height
3.390 inches minimum and 3.450 inches maximum
-
Overall Length
4.260 inches maximum
-
Reset Method
manual
-
Trip Delay Time In Seconds Per Rated Continuous Current
7.000 minimum at 200 pct all locations and 40.000 maximum at 200 pct all locations
-
Body Style
rectangular dimensional envelope
-
Circuit Protection Type
overcurrent all locations