Circuit Breakers
CIRCUIT BREAKER
AA1-B0-24-610-1B1-C
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
magnetic single location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.660 inches nominal
-
Thread Series Designator
unc
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Body Length
2.000 inches nominal
-
Inclosure Protection Type For Which Designed
moisture resistant and shock resistant and salt spray proof and vibration resistant
-
Operating Voltage Type And Rating Per Pole In Volts
277.0 ac single location
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Pole Quantity
1
-
Center To Center Distance Between Terminals Parallel To Length
1.560 inches nominal
-
Mounting Surface To Terminal End Distance
2.000 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Frequency In Hertz
50.0 single location or 60.0 single location
-
Terminal Type And Quantity
2 quick disconnect, male
-
Body Style
single pole type
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.200 minimum at 200 pct single location and 20.000 maximum at 200 pct single location
-
Body Width
0.755 inches nominal
-
Features Provided
high inrush protection
-
Case Material
plastic
-
Boss Height
0.130 inches nominal