Technical Characteristics
-
Actuator Function
reset
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
200.0 all locations
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Reset Method
manual
-
Nominal Thread Size
0.500 inches
-
Trip Release Characteristic
time delay all locations
-
Internal Trip Release Configuration
series trip all locations
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic all locations
-
Body Style
multipole-multiple actuator type
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations and 50.0 dc all locations
-
Bushing Length
0.458 inches minimum and 0.478 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.000 minimum at 200 pct all locations and 15.000 maximum at 200 pct all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.095 inches minimum and 1.155 inches maximum
-
Body Length
1.365 inches minimum and 1.385 inches maximum
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Terminal Type And Quantity
4 tab, solder lug
-
Manual Actuator Type And Quantity
2 toggle
-
Maximum Continuous Load Current Rating Per Pole
1.5 amperes dc all locations
-
Thread Series Designator
un
-
Mounting Surface To Terminal End Distance
2.090 inches nominal
-
Case Material
plastic