AM2R-D3-LC07D-A-15-2
Circuit Breakers
CIRCUIT BREAKER
AM2R-D3-LC07D-A-15-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
on certain environmental and performance requ
-
Test Data Document
mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data
-
Case Material
plastic
-
Features Provided
high inrush protection
-
End Item Identification
missle, minuteman lgm-30, run in console
-
External Actuator Linkage Arrangement
one and two linked
-
Terminal Type And Quantity
4 threaded stud
-
Boss Height
0.109 inches minimum and 0.171 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations and 15.0 amperes dc all locations
-
Body Width
1.469 inches minimum and 1.531 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.909 inches minimum and 1.971 inches maximum
-
Manual Actuator Type And Quantity
2 toggle
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.719 inches minimum and 0.781 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.031 inches minimum and 2.093 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 80.0 dc all locations
-
Mounting Surface To Terminal End Distance
1.829 inches minimum and 1.891 inches maximum
-
Nominal Thread Size
0.138 inches
-
Body Length
2.469 inches minimum and 2.531 inches maximum
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic-hydraulic all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.719 inches minimum and 0.781 inches maximum
-
Mounting Facility Type And Quantity
4 threaded hole
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 all locations
-
Internal Trip Release Configuration
series trip all locations
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Part Name Assigned By Controlling Agency
circuit breaker
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.700 minimum at 200 pct all locations and 18.000 maximum at 200 pct all locations
-
Reset Method
manual
-
Actuator Position Designation
at each pole
-
Thread Series Designator
unc
-
Pole Quantity
2
-
Circuit Protection Type
overcurrent all locations