NSN: 5925-00-011-6642

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Mounting Surface To Terminal End Distance

    2.461 inches minimum and 2.481 inches maximum

  • Pole Quantity

    1

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Thread Quantity Per Inch

    32

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac

  • Circuit Protection Type

    overcurrent

  • Trip Release Method

    magnetic-hydraulic

  • Trip Release Characteristic

    time delay

  • Ultimate Trip Time Per Pole In Seconds

    1.500 minimum and 6.000 maximum

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Auxiliary Switch Function And Quantity

    1 control

  • Nominal Thread Size

    0.138 inches

  • Switch Location And Position Designation

    internal at pole one

  • Switch Terminal Type

    tab,solder lug

  • Switch Current Rating And Type In Amps

    2.5 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Thread Series Designator

    unc

  • Body Width

    0.730 inches minimum and 0.740 inches maximum

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Switch Contact Arrangement

    single pole,double throw

  • Fragility Factor

    moderately rugged

  • Arc Quenching Method

    magnetic blowout

  • Storage Type

    general purpose warehouse

  • Maximum Continuous Load Current Rating Per Pole

    35.0 amperes ac

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Position Designation

    at pole one

  • Internal Trip Release Configuration

    series trip

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.300 minimum at 200 pct and 0.900 maximum at 200 pct

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Frequency In Hertz

    60.0

  • Unpackaged Unit Weight

    4.250 ounces

  • Terminal Type And Quantity

    2 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.