NSN: 5925-00-021-8039
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Thread Series Designator
unc
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.175 minimum at 200 pct single location and 0.550 maximum at 200 pct single location
-
Actuator Function
trip-reset
-
Body Width
1.020 inches minimum and 1.040 inches maximum
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Body Length
4.740 inches minimum and 4.760 inches maximum
-
Body Height
2.600 inches minimum and 2.620 inches maximum
-
Pole Quantity
1
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc single location
-
Maximum Continuous Load Current Rating Per Pole
75.0 amperes dc single location
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Unthreaded Mounting Hole Diameter
0.164 inches nominal
-
Inclosure Protection Type For Which Designed
dustproof and fungus proof
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.740 inches minimum and 2.760 inches maximum
-
Body Style
single pole type
-
Mounting Facility Type And Quantity
2 threaded hole and 1 unthreaded hole
-
Trip Release Method
magnetic-hydraulic single location
-
Center To Center Distance Between Terminals Parallel To Length
4.370 inches minimum and 4.390 inches maximum
-
Terminal Type And Quantity
2 compression
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 dc single location
-
Case Material
plastic