NSN: 5925-00-076-9310

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Mounting Surface To Terminal End Distance

    3.239 inches nominal

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    70.0 amperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Center To Center Distance Between Terminals Parallel To Width

    1.021 inches minimum and

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.740 inches minimum and

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.760 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.041 inches maximum

  • Boss Height

    0.146 inches minimum and

  • Boss Height

    0.166 inches maximum

  • Body Style

    8c multipole-multiple actuator type

  • Body Length

    3.729 inches maximum

  • Body Width

    3.062 inches maximum

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    3.053 inches minimum and

  • Center To Center Distance Between Terminals Parallel To Length

    3.073 inches maximum

  • Center To Center Distance Between Terminals Parallel To Width

    1.041 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.021 inches minimum and

  • Iii Fragility Factor

    moderately rugged

  • Iii Arc Quenching Method

    magnetic blowout

  • Iii Storage Type

    general purpose warehouse

  • Trip Release Method

    magnetic-hydraulic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    3 toggle

  • Internal Trip Release Configuration

    series trip all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    105.000 maximum at 200 pct all locations

  • Inclosure Protection Type For Which Designed

    fungus proof

  • Thread Series Designator

    unc

  • Terminal Type And Quantity

    6 threaded stud

  • Body Length

    3.709 inches minimum and

  • Body Width

    3.042 inches minimum and

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1500.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Characteristic

    time delay all locations

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at each pole

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Nominal Thread Size

    0.138 inches

  • Trip Delay Time In Seconds Per Rated Continuous Current

    35.000 minimum at 200 pct and

  • Inclosure Protection Type For Which Designed

    dustproof and

  • Frequency In Hertz

    60.0 all locations

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...