Technical Characteristics

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Body Width

    4.125 inches nominal

  • Reset Method

    manual

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Manual Actuator Type And Quantity

    1 toggle

  • Frequency In Hertz

    60.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    15000.0 ac all locations

  • Boss Height

    0.125 inches nominal

  • Terminal Type And Quantity

    6 screw

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac all locations

  • Body Length

    6.000 inches nominal

  • Trip Delay Time In Seconds Per Rated Continuous Current

    30.000 minimum at 200 pct all locations and 85.000 maximum at 200 pct all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.375 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    5.062 inches nominal

  • Body Height

    3.375 inches nominal

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac all locations

  • Case Material

    plastic

  • Unthreaded Mounting Hole Diameter

    0.187 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.500 inches nominal

  • Trip Release Ambient Temp Rating

    50.0 deg celsius maximum all locations

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Actuator Position Designation

    at pole two

  • Body Style

    multipole-single actuator type

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...