NSN: 5925-00-110-0742
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Trip Release Characteristic
instantaneous all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.719 inches nominal
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Body Length
10.125 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Center To Center Distance Between Terminals Parallel To Width
1.719 inches nominal
-
Boss Height
0.281 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
550.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
-
Case Material
plastic
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Body Style
multipole-single actuator type
-
Manual Actuator Type And Quantity
1 toggle
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
8.875 inches nominal
-
Unthreaded Mounting Hole Diameter
0.250 inches nominal
-
Trip Release Method
thermal-magnetic all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
8.438 inches nominal
-
Body Height
4.062 inches nominal
-
Actuator Position Designation
at pole two
-
Body Width
5.500 inches nominal
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations
-
Frequency In Hertz
60.0 all locations
-
Terminal Type And Quantity
6 compression