NSN: 5925-00-133-5365
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches minimum and 0.770 inches maximum
-
Fragility Factor
moderately rugged
-
Switch Terminal Type
tab, solder lug
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.940 inches maximum
-
Internal Trip Release Configuration
relay trip fourth location
-
Frequency In Hertz
400.0 all locations
-
Body Width
3.060 inches maximum
-
Auxiliary Switch Function And Quantity
1 alarm
-
Manual Actuator Type And Quantity
4 toggle
-
Case Material
plastic
-
Pole Quantity
4
-
Boss Height
0.150 inches maximum
-
Trip Release Characteristic
time delay third location
-
Trip Release Characteristic
instantaneous fourth location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
External Actuator Linkage Arrangement
two, three, and four linked
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.600 minimum at 200 pct first location and 5.000 maximum at 200 pct first location
-
Terminal Type And Quantity
10 threaded stud
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.600 minimum at 200 pct third location and 5.000 maximum at 200 pct third location
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Switch Location And Position Designation
internal at pole three
-
Storage Type
general purpose warehouse
-
Switch Current Rating And Type In Amps
5.0 ac and 1.0 dc
-
Actuator Function
trip-reset
-
Mounting Surface To Terminal End Distance
2.522 inches maximum
-
Switch Voltage Rating And Type In Volts
125.0 ac and 50.0 dc
-
Body Length
2.530 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.600 minimum at 200 pct second location and 5.000 maximum at 200 pct second location
-
Trip Release Characteristic
time delay first location
-
Switch Contact Arrangement
single pole, double throw
-
Specification/Standard Data
12436-a15912 government specification
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches minimum and 0.770 inches maximum
-
Internal Trip Release Configuration
series trip second location
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay second location
-
Internal Trip Release Configuration
series trip third location
-
Main Contact Tripping Mechanism Type
trip free
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant and fungus resistant and moisture resistant and explosion proof
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.050 inches minimum and 2.070 inches maximum
-
Thread Quantity Per Inch
32
-
Mounting Facility Type And Quantity
8 threaded hole
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Internal Trip Release Configuration
series trip first location