NSN: 5925-00-137-4504
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations
-
~1
data on certain environmental and performanc
-
Test Data Document
81349-mil-c-39019 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Switch Terminal Type
tab, solder lug
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Bushing Length
0.280 inches minimum and 0.380 inches maximum
-
Reset Method
manual
-
Switch Location And Position Designation
internal at pole three
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Actuator Position Designation
at pole two
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Switch Contact Arrangement
single pole, double throw
-
Body Style
multipole-single actuator type
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Switch Current Rating And Type In Amps
0.5 ac and 0.5 dc
-
Body Width
1.562 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
0.906 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
9.000 maximum at 200 pct all locations and 0.500 minimum at 200 pct all locations and 1.750 maximum at 400 pct all locations
-
Frequency In Hertz
400.0 all locations
-
Thread Series Designator
unef
-
Switch Voltage Rating And Type In Volts
120.0 ac and 50.0 dc
-
Auxiliary Switch Function And Quantity
1 alarm
-
Maximum Continuous Load Current Rating Per Pole
7.0 amperes ac all locations
-
Body Length
1.937 inches maximum
-
Ultimate Trip Time Per Pole In Seconds
3.000 minimum all locations and 60.000 maximum all locations
-
Terminal Type And Quantity
6 wire hook
-
Trip Release Characteristic
time delay all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Mounting Facility Type And Quantity
thd bushing w/panel seal
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Trip Release Method
magnetic all locations