NSN: 5925-00-156-4006
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Maximum Continuous Load Current Rating Per Pole
500.0 amperes dc first location
-
Terminal Type And Quantity
6 wire hook
-
Unpackaged Unit Weight
5.400 ounces
-
Maximum Continuous Load Current Rating Per Pole
6.0 amperes ac third location
-
Thread Series Designator
unef
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc second location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Body Width
1.937 inches maximum
-
Body Length
1.500 inches maximum
-
Manual Actuator Type And Quantity
1 toggle
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 dc second location
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc first location
-
Case Material
metal
-
Body Style
multipole-single actuator type
-
Bushing Length
0.375 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 dc first location
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Actuator Position Designation
at pole two
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Trip Release Method
magnetic all locations
-
Thread Quantity Per Inch
32
-
Nominal Thread Size
0.375 inches
-
Internal Trip Release Configuration
series trip all locations
-
Actuator Function
trip-reset
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.055 minimum at 200 pct all locations and 0.950 maximum at 200 pct all locations
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Reset Method
manual
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Special Handling Feature
magnetic
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac third location
-
Fragility Factor
moderately rugged
-
Frequency In Hertz
440.0 third location
-
Maximum Continuous Load Current Rating Per Pole
500.0 amperes dc second location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac third location
-
Inclosure Protection Type For Which Designed
shockproof and hermetically sealed and vibrationproof