NSN: 5925-00-159-7565
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Arc Quenching Method
magnetic blowout
-
Thread Quantity Per Inch
24
-
Body Width
1.250 inches maximum
-
Internal Trip Release Configuration
shunt trip second location
-
Switch Terminal Type
pin
-
Switch Current Rating And Type In Amps
0.500 ac
-
Inclosure Protection Type For Which Designed
shock resistant and hermetically sealed and vibration resistant
-
Auxiliary Switch Function And Quantity
1 alarm
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.200 minimum at 200 pct second location and 6.000 maximum at 200 pct second location
-
Bushing Length
0.332 inches minimum and 0.375 inches maximum
-
Special Features
shunt coil rating is 0.500 amps,240 vac,60 hz
-
Switch Location And Position Designation
internal at pole one
-
Fragility Factor
moderately rugged
-
Nonturn Device Diameter
0.250 inches nominal
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 32.0 dc all locations
-
Pole Quantity
2
-
Terminal Type And Quantity
5 wire hook
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Thread Series Designator
unf
-
Storage Type
general purpose warehouse
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Actuator Function
trip-reset
-
Nominal Thread Size
0.375 inches
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations and 1000.0 dc all locations
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations and 20.0 amperes dc all locations
-
Trip Release Method
magnetic all locations
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Internal Trip Release Configuration
series trip first location
-
Switch Contact Arrangement
single pole, double throw
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Nonturn Device Location
at 3 oclock and at 9 oclock
-
Body Style
multipole-single actuator type
-
Nonturn Device Radius
0.625 inches nominal
-
Trip Release Characteristic
instantaneous first location
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Trip Release Characteristic
time delay second location
-
Switch Voltage Rating And Type In Volts
120.0 ac
-
Body Length
1.500 inches maximum
-
Actuator Position Designation
between pole one and two