Technical Characteristics

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Center To Center Distance Between Terminals Parallel To Width

    1.000 inches nominal

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Nominal Thread Size

    0.138 inches

  • Main Contact Tripping Mechanism Type

    trip free

  • Boss Height

    0.160 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1500.0 ac all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.030 inches nominal

  • Frequency In Hertz

    400.0 all locations

  • Body Width

    3.060 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.750 inches nominal

  • Body Length

    3.730 inches nominal

  • Manual Actuator Type And Quantity

    3 toggle

  • Unpackaged Unit Weight

    1.770 pounds

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

  • Operating Voltage Type And Rating Per Pole In Volts

    208.0 ac all locations

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.130 minimum at 200 pct all locations and 1.000 maximum at 200 pct all locations

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Continuous Load Current Rating Per Pole

    70.0 amperes ac all locations

  • Center To Center Distance Between Terminals Parallel To Length

    3.060 inches nominal

  • Mounting Surface To Terminal End Distance

    3.250 inches nominal

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Style

    multipole-multiple actuator type

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...