NSN: 5925-00-190-0028
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Ultimate Trip Time Per Pole In Seconds
20.000 minimum all locations and 80.000 maximum all locations
-
Center To Center Distance Between Terminals Parallel To Length
3.063 inches nominal
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Body Width
3.052 inches nominal
-
Mounting Facility Type And Quantity
6 threaded hole
-
Body Style
multipole-single actuator type
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Boss Height
0.156 inches nominal
-
Frequency In Hertz
50.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Delay Time In Seconds Per Rated Continuous Current
19.000 maximum at 200 pct all locations and 1.100 minimum at 400 pct all locations and 5.500 minimum at 200 pct all locations and 3.000 maximum at 400 pct all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.031 inches nominal
-
Case Material
plastic
-
Terminal Type And Quantity
6 threaded stud
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Center To Center Distance Between Terminals Parallel To Width
1.031 inches nominal
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Body Length
3.719 inches nominal
-
Mounting Surface To Terminal End Distance
3.239 inches nominal