NSN: 5925-00-196-3997
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
6 bus bar
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
-
Body Height
17.000 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac all locations
-
Switch Current Rating And Type In Amps
12.0 ac and 9.0 dc
-
Mounting Facility Type And Quantity
4 slot and 4 unthreaded hole
-
Body Length
17.562 inches nominal
-
Body Width
12.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
3.625 inches nominal
-
Switch Voltage Rating And Type In Volts
208.0 ac and 120.0 dc
-
Special Features
long delay pickup,long time delayband,instantaneous pickup settings adjustable.
-
Boss Height
0.375 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Internal Trip Release Configuration
shunt trip all locations
-
Frequency In Hertz
60.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.375 inches nominal
-
Mounting Slot Width
0.187 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
600.0 amperes ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
11.625 inches nominal
-
Manual Actuator Type And Quantity
1 rotary
-
Case Material
metal
-
Ultimate Trip Time Per Pole In Seconds
56.000 nominal all locations
-
Body Style
multipole-single actuator type
-
Unthreaded Mounting Hole Diameter
0.500 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Trip Release Method
magnetic all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Adjustable Trip Setting Current Range Per Pole In Amps
+280.0/+460.0 ac all locations and +1750.0/+5250.0 ac all locations
-
Actuator Position Designation
at pole one
-
Features Provided
adjustable trip release
-
Switch Terminal Type
threaded stud
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Reset Actuator Voltage Rating And Type In Volts
208.0 ac
-
Reset Method
electric
-
Auxiliary Switch Function And Quantity
12 alarm
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
10.562 inches nominal
-
Actuator Function
reset
-
Trip Delay Time In Seconds Per Rated Continuous Current
75.000 minimum at 100 pct all locations and 1000.000 maximum at 100 pct all locations and 56.000 minimum at 150 pct all locations and 46.000 minimum at 200 pct all locations and 34.000 minimum at 400 pct all locations and 28.000 minimum at 500 pct all
-
~1
locations and 90.000 maximum at 400 pct all loca