NSN: 5925-00-208-4081
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Center To Center Distance Between Terminals Parallel To Length
6.562 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
150.000 minimum at 200 pct all locations and 275.000 maximum at 200 pct all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
7.125 inches nominal
-
Reset Method
manual
-
Center To Center Distance Between Terminals Parallel To Width
1.500 inches nominal
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Body Width
4.500 inches nominal
-
Body Length
8.000 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
125.0 amperes ac all locations
-
Trip Release Method
thermal-magnetic all locations
-
Actuator Position Designation
at pole two
-
Body Height
3.500 inches nominal
-
Body Style
multipole-single actuator type
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Terminal Type And Quantity
6 compression
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Unthreaded Mounting Hole Diameter
0.201 inches nominal
-
Trip Release Ambient Temp Rating
40.0 deg celsius maximum all locations
-
Boss Height
0.125 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
30000.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.500 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
-
Case Material
plastic