NSN: 5925-00-227-0381
Circuit Breakers
TRIPPER,CIRCUIT BREAKER
TRIPPER,CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Body Style
rectangular dimensional envelope
-
Features Provided
adjustable trip release
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Mounting Facility Type And Quantity
3 terminal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Overall Length
4.500 inches nominal
-
Adjustable Trip Setting Current Range Per Pole In Amps
+1200.0/+1400.0 ac all locations
-
Terminal Type And Quantity
6 screw
-
Overall Height
3.625 inches nominal
-
Frequency In Hertz
400.0 all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
3600.000 nominal at 150 pct all locations
-
Overall Width
3.875 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations