NSN: 5925-00-227-0387
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Thread Series Designator
unc
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Precious Material
silver
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
122.0 single location
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Center To Center Distance Between Terminals Parallel To Length
1.796 inches minimum and 1.828 inches maximum
-
Pole Quantity
1
-
Arc Quenching Method
deion
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Mounting Surface To Terminal End Distance
2.554 inches minimum and 2.624 inches maximum
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.625 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location and 5000.0 dc single location
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud
-
Body Length
2.985 inches minimum and 3.016 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 ac single location and 32.0 dc single location
-
Nominal Thread Size
0.164 inches
-
Precious Material And Location
contact surfaces silver
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location and 15.0 amperes dc single location
-
Boss Height
0.005 inches nominal
-
Inclosure Protection Type For Which Designed
general purpose
-
Body Style
single pole type
-
Frequency In Hertz
60.0 single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
12.800 minimum at 200 pct single location and 38.000 maximum at 200 pct single location
-
Body Width
1.000 inches maximum