NSN: 5925-00-238-3073
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
1d rectangular dimensional envelope
-
Case Material
plastic
-
Unthreaded Mounting Hole Diameter
0.187 inches nominal
-
Mounting Facility Type And Quantity
2 unthreaded hole
-
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac all locations and 250.0 dc
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Characteristic
time delay all locations
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole one
-
Trip Release Ambient Temp Rating
40.0 deg celsius maximum all locations
-
Overall Length
6.000 inches nominal
-
Overall Height
3.969 inches nominal
-
Overall Width
2.750 inches nominal
-
Pole Quantity
2
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations and 20.0 amperes dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac all locations and 10000.0 dc
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Actuator Function
trip-reset
-
Trip Delay Time In Seconds Per Rated Continuous Current
30.000 minimum at 200 pct all locations and 85.000 maximum at 200 pct
-
Frequency In Hertz
60.0 all locations
-
Terminal Type And Quantity
4 screw