Technical Characteristics
-
Fragility Factor
moderately rugged
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Body Width
4.125 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
3600.000 nominal at 125 pct all locations and 33.000 nominal at 200 pct all locations and 14.000 nominal at 300 pct all locations
-
Reset Method
manual
-
Terminal Type And Quantity
6 tab, solder lug
-
Storage Type
general purpose warehouse
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.500 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Actuator Position Designation
at pole two
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Body Style
multipole-single actuator type
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Arc Quenching Method
magnetic blowout
-
Boss Height
0.125 inches nominal
-
Unthreaded Mounting Hole Diameter
0.188 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations
-
Body Length
6.000 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
5.062 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
18000.0 ac all locations
-
Body Height
3.375 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
-
Case Material
plastic
-
Trip Release Method