NSN: 5925-00-252-4204

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac single location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac single location

  • Circuit Protection Type

    overcurrent single location

  • Ultimate Trip Time Per Pole In Seconds

    3.000 minimum and 50.000 maximum single location

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Position Designation

    at pole one

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Switch Current Rating And Type In Amps

    10.0 ac and 2.5 dc

  • Thread Series Designator

    unc

  • Body Width

    0.750 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    1.530 inches nominal

  • Switch Contact Arrangement

    single pole, double throw

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Iii Storage Type

    general purpose warehouse

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac single location

  • Trip Release Method

    magnetic-hydraulic single location

  • Trip Release Characteristic

    time delay single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 single location

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip single location

  • Nominal Thread Size

    0.138 inches

  • Switch Location And Position Designation

    external at pole one

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.000 minimum at 200 pct and 20.000 maximum at 200 pct single location

  • Switch Terminal Type

    tab, solder lug

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 30.0 dc

  • Frequency In Hertz

    60.0 single location

  • Iii Unpackaged Unit Weight

    2.500 ounces

  • Terminal Type And Quantity

    2 tab, solder lug

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    1.660 inches nominal

  • Iii Fragility Factor

    moderately rugged

  • Boss Height

    0.130 inches nominal

  • Mounting Surface To Terminal End Distance

    2.000 inches nominal

  • Pole Quantity

    1

  • Iii Arc Quenching Method

    magnetic blowout

  • Iii Special Handling Feature

    magnetic

  • Body Style

    12a single pole type

  • Body Length

    2.000 inches nominal

  • Case Material

    plastic

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...