NSN: 5925-00-257-9108
Circuit Breakers
TRIPPER,CIRCUIT BREAKER
TRIPPER,CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Overall Height
4.250 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 terminal
-
Circuit Protection Type
overcurrent all locations
-
Body Style
rectangular dimensional envelope
-
Actuator Position Designation
at each pole
-
Features Provided
adjustable trip release
-
Adjustable Trip Setting Current Range Per Pole In Amps
+1700.0/+3400.0 ac all locations and +1850.0/+3800.0 dc all locations
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations and 250.0 dc all locations
-
Actuator Function
trip-reset
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Overall Width
4.625 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Overall Length
8.438 inches nominal
-
Terminal Type And Quantity
6 screw
-
Trip Delay Time In Seconds Per Rated Continuous Current
3600.000 nominal at 150 pct all locations
-
Maximum Continuous Load Current Rating Per Pole
250.0 amperes ac all locations and 250.0 amperes dc all locations