NSN: 5925-00-258-1973
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
1
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Nominal Thread Size
0.164 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.400 minimum at 300 pct single location and 1.700 maximum at 200 pct single location and 1.000 minimum at 200 pct single location and 3.600 minimum at 125 pct single location and 6.000 maximum at 125 pct single location and 0.620 maximum at 300 pct
-
Trip Release Method
magnetic single location
-
Overall Length
5.125 inches nominal
-
Thread Series Designator
unc
-
Overall Height
5.875 inches nominal
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3000.0 ac single location
-
Overall Width
1.500 inches nominal
-
Circuit Protection Type
overcurrent single location
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 ac single location
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac single location
-
Frequency In Hertz
60.0 single location
-
Reset Method
automatic
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud
-
~1
single location