NSN: 5925-00-258-2878
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
2 threaded stud
-
Mounting Surface To Terminal End Distance
2.328 inches nominal
-
Case Material
plastic
-
Reset Method
automatic
-
Maximum Continuous Load Current Rating Per Pole
80.0 amperes ac single location and 80.0 amperes dc single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
4000.0 ac single location and 4000.0 dc single location
-
Center To Center Distance Between Terminals Parallel To Length
2.625 inches nominal
-
Frequency In Hertz
60.0 single location
-
Overall Length
3.625 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.125 inches nominal
-
Body Style
single pole type
-
Unthreaded Mounting Hole Diameter
0.203 inches nominal
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Trip Release Characteristic
time delay single location
-
Mounting Facility Type And Quantity
2 unthreaded hole
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 200 pct single location and 100.000 maximum at 200 pct single location
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 ac single location and 28.0 dc single location
-
Internal Trip Release Configuration
series trip single location
-
Pole Quantity
1
-
Body Width
1.375 inches nominal
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Trip Release Method
thermal single location
-
Circuit Protection Type
overcurrent single location