NSN: 5925-00-265-9487
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Overall Height
3.500 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac first location
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
6.000 minimum at 300 pct all locations and 50.000 maximum at 200 pct all locations and 20.000 minimum at 200 pct all locations and 252.000 nominal at 125 pct all locations and 10.000 maximum at 300 pct all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Overall Width
4.875 inches nominal
-
Trip Release Method
thermal all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac second location
-
Thread Quantity Per Inch
32
-
Mounting Facility Type And Quantity
4 threaded hole
-
Terminal Type And Quantity
4 screw
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Reset Method
manual
-
Thread Series Designator
unc
-
Pole Quantity
2
-
Trip Release Ambient Temp Rating
75.0 deg fahrenheit nominal all locations
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Overall Length
9.000 inches nominal