NSN: 5925-00-269-2628

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Length

    5.219 inches nominal

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    15000.0 ac all locations and 10000.0 dc all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac all locations and 250.0 dc all locations

  • Body Height

    3.406 inches nominal

  • Case Material

    plastic

  • Trip Delay Time In Seconds Per Rated Continuous Current

    24.000 minimum at 200 pct all locations and 65.000 maximum at 200 pct all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Actuator Position Designation

    between pole one and two

  • Frequency In Hertz

    60.0 all locations

  • Manual Actuator Type And Quantity

    1 toggle

  • Boss Height

    0.250 inches nominal

  • Terminal Type And Quantity

    4 compression

  • Body Style

    multipole-single actuator type

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Trip Release Method

    thermal-magnetic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Body Width

    2.750 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    5.125 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Trip Release Ambient Temp Rating

    50.0 deg celsius maximum all locations

  • Mounting Slot Width

    0.370 inches nominal

  • Trip Release Characteristic

    instantaneous all locations and time delay all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    2.500 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    90.0 amperes ac all locations and 90.0 amperes dc all locations

  • Actuator Function

    trip-reset

  • Storage Type

    general purpose warehouse

  • Reset Method

    manual

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    4 slot

  • Circuit Protection Type

    overcurrent all locations

  • Body Length

    6.062 inches nominal

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...