NSN: 5925-00-270-6002
Circuit Breakers
TRIPPER,CIRCUIT BREAKER
TRIPPER,CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 terminal
-
Circuit Protection Type
overcurrent all locations
-
Body Style
rectangular dimensional envelope
-
Overall Width
3.312 inches nominal
-
Features Provided
adjustable trip release
-
Overall Height
3.188 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
122.0 all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
108.000 minimum at 200 pct all locations and 360.000 maximum at 200 pct all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Frequency In Hertz
60.0 all locations
-
Adjustable Trip Setting Current Range Per Pole In Amps
+400.0/+1000.0 ac all locations
-
Terminal Type And Quantity
6 compression
-
Overall Length
7.438 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations