NSN: 5925-00-274-1296

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Length

    10.750 inches nominal

  • Body Height

    4.062 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    2.750 inches nominal

  • Boss Height

    0.250 inches nominal

  • Features Provided

    adjustable trip release

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    25000.0 ac and 20000.0 dc

  • Trip Release Method

    thermal-magnetic

  • Trip Release Characteristic

    time delay

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Reset Method

    manual

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole two

  • Adjustable Trip Setting Current Range Per Pole In Amps

    p1500.0/p3000.0 ac and p1500.0/p3000.0 dc

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal

  • Terminal Type And Quantity

    6 compression

  • Body Width

    8.250 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    9.531 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.312 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    9.531 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    2.750 inches nominal

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Maximum Continuous Load Current Rating Per Pole

    300.0 amperes ac and 300.0 amperes dc

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac and 48.0 dc

  • Circuit Protection Type

    overcurrent

  • Main Contact Tripping Mechanism Type

    trip free

  • Trip Delay Time In Seconds Per Rated Continuous Current

    90.000 minimum at 200 pct and 550.000 maximum at 200 pct

  • Inclosure Protection Type For Which Designed

    dustproof

  • Frequency In Hertz

    60.0

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...