Technical Characteristics
-
Actuator Function
trip-reset
-
Reset Method
manual
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
120.0 single location
-
Case Material
plastic
-
Overall Length
2.000 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac single location and 20.0 amperes dc single location
-
Unthreaded Mounting Hole Diameter
0.188 inches nominal
-
Manual Actuator Type And Quantity
2 push button
-
Operating Voltage Type And Rating Per Pole In Volts
30.0 ac single location and 30.0 dc single location
-
Inclosure Protection Type For Which Designed
shockproof and vibrationproof
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Trip Release Characteristic
time delay single location
-
Mounting Facility Type And Quantity
2 unthreaded hole
-
Overall Height
1.531 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
100.000 nominal at 125 pct single location and 7.500 nominal at 200 pct single location and 1.900 nominal at 300 pct single location
-
Pole Quantity
1
-
Overall Width
1.188 inches nominal
-
Trip Release Method
thermal single location
-
Circuit Protection Type
overcurrent single location
-
Terminal Type And Quantity
2 screw
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
400.0 ac single location and 400.0 dc single location