NSN: 5925-00-356-8007
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Trip Release Ambient Temp Rating
25.0 deg celsius maximum all locations
-
Bushing Length
0.250 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.500 minimum at 200 pct all locations and 40.000 maximum at 200 pct all locations
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Thread Quantity Per Inch
32
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Body Length
1.094 inches maximum
-
Manual Actuator Type And Quantity
1 push-pull
-
Unpackaged Unit Weight
3.500 ounces
-
Actuator Position Designation
at pole two
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Center To Center Distance Between Terminals Parallel To Width
0.780 inches nominal
-
Body Style
multipole-single actuator type
-
Maximum Continuous Load Current Rating Per Pole
35.0 amperes ac all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Center To Center Distance Between Terminals Parallel To Length
0.704 inches nominal
-
Body Width
2.350 inches maximum
-
Frequency In Hertz
400.0 all locations
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
140.0 all locations
-
Terminal Type And Quantity
6 tab w/screw
-
Nominal Thread Size
0.469 inches
-
Body Height
1.600 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2500.0 ac all locations
-
Thread Series Designator
uns
-
Case Material
plastic
-
Trip Release Method
thermal all locations