NSN: 5925-00-402-1034

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Length

    7.000 inches nominal

  • Body Width

    4.500 inches nominal

  • Body Height

    2.906 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    6.125 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.250 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.500 inches nominal

  • Fragility Factor

    moderately rugged

  • Boss Height

    0.218 inches nominal

  • Pole Quantity

    3

  • Special Handling Feature

    magnetic

  • Maximum Continuous Load Current Rating Per Pole

    125.0 amperes ac .

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole two

  • Internal Trip Release Configuration

    series trip .

  • Frequency In Hertz

    60.0

  • Body Style

    caaql 11b

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Width

    1.500 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.359 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Storage Type

    general purpose warehouse

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac .

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    10000.0 ac .

  • Circuit Protection Type

    overcurrent .

  • Trip Release Method

    magnetic-hydraulic .

  • Trip Release Characteristic

    time delay .

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Trip Delay Time In Seconds Per Rated Continuous Current

    25.000 minimum at 200 pct and 190.000 maximum at 200 pct .

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Terminal Type And Quantity

    6 compression

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...