NSN: 5925-00-403-4170

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Frequency In Hertz

    60.0 all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Trip Delay Time In Seconds Per Rated Continuous Current

    50.000 maximum at 300 pct all locations and 30.000 maximum at 325 pct

  • Trip Release Ambient Temp Rating

    50.0 deg celsius nominal all locations

  • Terminal Type And Quantity

    6 compression

  • Body Width

    4.125 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    5.562 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.188 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.938 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.375 inches nominal

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Storage Type

    general purpose warehouse

  • Maximum Continuous Load Current Rating Per Pole

    30.0 amperes ac all locations and 30.0 amperes dc

  • Trip Release Characteristic

    instantaneous all locations and time delay

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    135.0 all locations

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole two

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Body Style

    11b multipole-single actuator type

  • Body Length

    6.500 inches nominal

  • Body Height

    3.375 inches nominal

  • Boss Height

    0.125 inches nominal

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac all locations and 250.0 dc

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    100000.0 ac all locations and 100000.0 dc

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...