NSN: 5925-00-433-6125
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
2.250 inches maximum
-
Fragility Factor
moderately rugged
-
Body Height
2.460 inches minimum and 2.480 inches maximum
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Reset Method
manual
-
Switch Location And Position Designation
internal at pole three
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
145.0 all locations
-
Switch Terminal Type
wire lead
-
Thread Quantity Per Inch
32
-
Trip Release Method
thermal-magnetic all locations
-
Manual Actuator Type And Quantity
1 push-pull
-
Actuator Position Designation
at pole two
-
Switch Contact Arrangement
single pole, double throw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.800 inches minimum and 1.820 inches maximum
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Mounting Facility Type And Quantity
6 threaded hole
-
Body Style
multipole-single actuator type
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Body Length
2.189 inches maximum
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
4200.0 ac all locations and 4200.0 dc all locations
-
Switch Voltage Rating And Type In Volts
28.0 dc
-
Switch Current Rating And Type In Amps
7.0 dc
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Bushing Length
0.235 inches minimum and 0.250 inches maximum
-
Unpackaged Unit Weight
0.700 pounds
-
Frequency In Hertz
400.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations and 25.0 amperes dc all locations
-
Auxiliary Switch Function And Quantity
1 alarm
-
Center To Center Distance Between Terminals Parallel To Length
1.180 inches minimum and 1.200 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
205.0 ac all locations and 50.0 dc all locations
-
Terminal Type And Quantity
6 tab w/screw
-
Trip Delay Time In Seconds Per Rated Continuous Current
22.000 minimum at 200 pct all locations and 55.000 maximum at 200 pct all locations
-
Case Material
plastic