Technical Characteristics

  • Body Length

    1.448 inches minimum and 1.510 inches maximum

  • Body Width

    0.567 inches minimum and 0.629 inches maximum

  • Case Material

    metal

  • Center To Center Distance Between Terminals Parallel To Length

    0.870 inches minimum and 0.880 inches maximum

  • Mounting Surface To Terminal End Distance

    1.524 inches minimum and 1.586 inches maximum

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Storage Type

    general purpose warehouse

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    2.0 amperes ac single location

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac single location

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac single location

  • Trip Release Method

    magnetic-hydraulic single location

  • Trip Release Characteristic

    time delay single location

  • Internal Trip Release Configuration

    series trip single location

  • Nominal Thread Size

    0.375 inches

  • Inclosure Protection Type For Which Designed

    vibrationproof

  • Thread Series Designator

    unef

  • Terminal Type And Quantity

    2 wire hook

  • Thread Pitch Diameters

    +0.3503/+0.3537 inches

  • Body Style

    2a single pole type

  • Bushing Length

    0.360 inches minimum and 0.380 inches maximum

  • Fragility Factor

    moderately rugged

  • Pole Quantity

    1

  • Circuit Protection Type

    overcurrent single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0

  • Ultimate Trip Time Per Pole In Seconds

    30.000 nominal single location

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole one

  • Trip Release Duty Cycle

    continuous single location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 maximum at 200 pct and 0.015 minimum at 400 pct and 0.100 maximum at 400 pct single location

  • Frequency In Hertz

    400.0

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...