NSN: 5925-00-455-7733
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.050 inches minimum and 2.070 inches maximum
-
Thread Quantity Per Inch
32
-
Switch Current Rating And Type In Amps
10.0 ac and 10.0 dc
-
Mounting Facility Type And Quantity
8 threaded hole
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes dc third location
-
Trip Release Characteristic
time delay first location
-
External Actuator Linkage Arrangement
one, two, three, and four linked
-
Switch Contact Arrangement
single pole, double throw
-
Trip Release Characteristic
time delay fourth location
-
Terminal Type And Quantity
8 threaded stud
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc first location
-
Nominal Thread Size
0.138 inches
-
Inclosure Protection Type For Which Designed
shockproof and vibrationproof and moisture resistant and corrosion resistant and fungus resistant
-
Boss Height
0.150 inches nominal
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Maximum Continuous Load Current Rating Per Pole
100.0 milliamperes dc second location
-
Body Width
3.015 inches maximum
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes dc first location
-
Center To Center Distance Between Terminals Parallel To Length
1.940 inches nominal
-
Trip Release Characteristic
time delay second location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.735 inches minimum and 0.765 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc fourth location
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.700 minimum at 200 pct first location and 10.000 maximum at 200 pct first location
-
Arc Quenching Method
magnetic blowout
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc second location
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.024 maximum at 200 pct fourth location
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Maximum Continuous Load Current Rating Per Pole
100.0 milliamperes dc fourth location
-
Reset Method
manual
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.735 inches minimum and 0.765 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 dc all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.024 maximum at 200 pct second location
-
Switch Location And Position Designation
internal at pole four
-
Switch Terminal Type
pin
-
Body Length
2.480 inches minimum and 2.500 inches maximum
-
Mounting Surface To Terminal End Distance
2.625 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc third location
-
Manual Actuator Type And Quantity
4 toggle
-
Unpackaged Unit Weight
14.800 ounces
-
Case Material
plastic
-
Pole Quantity
4
-
Trip Release Characteristic
instantaneous third location