NSN: 5925-00-477-2282
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
3.025 inches minimum and 3.065 inches maximum
-
Fragility Factor
moderately rugged
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
3 terminal
-
Maximum Continuous Load Current Rating Per Pole
60.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Characteristic
time delay all locations
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
Trip Delay Time In Seconds Per Rated Continuous Current
4.000 maximum at 200 pct all locations
-
Inclosure Protection Type For Which Designed
corrosion resistant
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Frequency In Hertz
60.0
-
Test Data Document
81348-w-c-375 specification
-
Terminal Type And Quantity
3 clip and 3 compression
-
Body Style
6c multipole-multiple actuator type
-
Body Width
2.193 inches minimum and 2.241 inches maximum
-
Body Height
2.371 inches minimum and 2.433 inches maximum
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches nominal
-
Boss Height
0.188 inches nominal
-
Storage Type
general purpose warehouse
-
Special Handling Feature
magnetic
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Specification/Standard Data
81348-w-c-375/7 government specification