NSN: 5925-00-484-4538
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Frequency In Hertz
420.0 all locations
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic all locations
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Test Data Document
80249-840069 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Terminal Type And Quantity
4 wire hook
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Body Style
multipole-single actuator type
-
Inclosure Protection Type For Which Designed
hermetically sealed and shockproof and vibrationproof
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Body Length
1.500 inches maximum
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations and 10.0 amperes dc all locations
-
Body Width
1.250 inches maximum
-
Thread Series Designator
unef
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.070 minimum at 200 pct all locations and 0.700 maximum at 200 pct all locations
-
Bushing Length
0.332 inches minimum and 0.375 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations
-
Unpackaged Unit Weight
4.000 ounces
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac all locations and 150.0 dc all locations