NSN: 5925-00-484-4541

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Case Material

    metal

  • Center To Center Distance Between Terminals Parallel To Length

    0.875 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    0.625 inches nominal

  • Nonturn Device Location

    at 3 oclock and at 9 oclock

  • Nonturn Device Radius

    0.625 inches nominal

  • Nonturn Device Length

    0.130 inches nominal

  • Mounting Surface To Terminal End Distance

    1.780 inches maximum

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Storage Type

    general purpose warehouse

  • Special Handling Feature

    magnetic

  • Trip Release Method

    magnetic all locations

  • Internal Trip Release Configuration

    series trip all locations

  • Nominal Thread Size

    0.375 inches

  • Inclosure Protection Type For Which Designed

    hermetically sealed

  • Thread Series Designator

    unef

  • Body Style

    1b multipole-single actuator type

  • Bushing Length

    0.380 inches maximum

  • Body Length

    1.500 inches maximum

  • Body Width

    1.250 inches maximum

  • Nonturn Device Diameter

    0.140 inches nominal

  • Fragility Factor

    moderately rugged

  • Arc Quenching Method

    magnetic blowout

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    120.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    between pole one and two

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.055 minimum at 200 pct and 0.950 maximum at 200 pct all locations

  • Frequency In Hertz

    60.0

  • Terminal Type And Quantity

    4 wire hook

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...