NSN: 5925-00-493-1562
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
magnetic single location
-
Maximum Continuous Load Current Rating Per Pole
500.0 milliamperes dc single location
-
Terminal Type And Quantity
2 wire hook
-
Switch Terminal Type
tab, solder lug
-
Bushing Length
0.280 inches minimum and 0.380 inches maximum
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Test Data Document
81349-mil-c-39019 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 dc single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Switch Current Rating And Type In Amps
0.5 ac and 0.5 dc
-
Body Length
1.562 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc single location
-
Center To Center Distance Between Terminals Parallel To Length
0.906 inches maximum
-
Body Style
single pole type
-
Body Width
0.625 inches maximum
-
Thread Series Designator
unef
-
Switch Voltage Rating And Type In Volts
120.0 ac and 50.0 dc
-
Mounting Surface To Terminal End Distance
1.700 inches maximum
-
Auxiliary Switch Function And Quantity
1 alarm
-
Switch Location And Position Designation
internal at pole one
-
~1
data on certain environmental and performanc
-
Manual Actuator Type And Quantity
1 toggle
-
Case Material
metal
-
Pole Quantity
1
-
Switch Contact Arrangement
single pole, double throw
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Circuit Protection Type
overcurrent single location
-
Thread Quantity Per Inch
32
-
Nominal Thread Size
0.375 inches
-
Ultimate Trip Time Per Pole In Seconds
3.000 minimum single location and 60.000 maximum single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct single location and 9.000 maximum at 200 pct single location and 1.750 maximum at 400 pct single location