Technical Characteristics

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Fragility Factor

    moderately rugged

  • Circuit Protection Type

    overcurrent all locations

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    between pole one and two

  • Nominal Thread Size

    0.164 inches

  • Inclosure Protection Type For Which Designed

    dustproof and fungus proof

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal all locations

  • Thread Series Designator

    unc

  • Body Style

    9b multipole-single actuator type

  • Body Width

    1.990 inches minimum and 2.010 inches maximum

  • Body Height

    2.677 inches minimum and 2.697 inches maximum

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    4.349 inches minimum and 4.369 inches maximum

  • Center To Center Distance Between Terminals Parallel To Width

    0.990 inches minimum and 1.010 inches maximum

  • Body Length

    5.240 inches minimum and 5.260 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    3.052 inches minimum and 3.072 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.974 inches minimum and 0.994 inches maximum

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    4 threaded hole and 2 unthreaded hole

  • Storage Type

    general purpose warehouse

  • Thread Quantity Per Inch

    32

  • Unthreaded Mounting Hole Diameter

    0.190 inches nominal

  • Boss Height

    0.208 inches minimum and 0.228 inches maximum

  • Pole Quantity

    2

  • Maximum Continuous Load Current Rating Per Pole

    30.0 amperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.200 minimum at 200 pct and 1.000 maximum at 200 pct all locations

  • Frequency In Hertz

    60.0

  • Terminal Type And Quantity

    4 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...