NSN: 5925-00-563-0263
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Thread Series Designator
unc
-
Frequency In Hertz
60.0
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.300 minimum at 200 pct and 1.000 maximum at 200 pct single location
-
Nominal Thread Size
0.138 inches
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Trip Release Characteristic
time delay single location
-
Trip Release Method
magnetic-hydraulic single location
-
Circuit Protection Type
overcurrent single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location
-
Thread Quantity Per Inch
32
-
Storage Type
general purpose warehouse
-
Pole Quantity
1
-
Case Material
plastic
-
Unpackaged Unit Weight
4.250 ounces
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Internal Trip Release Configuration
series trip single location
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Reset Method
manual
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac single location
-
Mounting Facility Type And Quantity
2 threaded hole
-
Arc Quenching Method
magnetic blowout
-
Mounting Surface To Terminal End Distance
2.471 inches nominal
-
Boss Height
0.140 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Body Width
0.750 inches nominal
-
Body Length
2.500 inches nominal
-
Body Style
12a single pole type
-
Terminal Type And Quantity
2 threaded stud