NSN: 5925-00-584-6271
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
data on certain environmental and performanc
-
Switch Terminal Type
tab, solder lug
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Maximum Continuous Load Current Rating Per Pole
500.0 milliamperes ac all locations
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Switch Location And Position Designation
internal at pole two
-
Trip Release Characteristic
time delay all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Actuator Function
trip-reset
-
Mounting Surface To Terminal End Distance
1.828 inches maximum
-
Internal Trip Release Configuration
series trip all locations
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.750 maximum at 400 pct all locations and 0.600 maximum at 600 pct all locations and 9.000 maximum at 200 pct all locations and 0.500 minimum at 200 pct all locations and 0.100 maximum at 800 pct all locations
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free
-
Switch Current Rating And Type In Amps
0.5 ac and 0.5 dc
-
Body Length
1.562 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
0.906 inches maximum
-
Frequency In Hertz
400.0 all locations
-
Thread Series Designator
unef
-
Switch Voltage Rating And Type In Volts
120.0 ac and 50.0 dc
-
Auxiliary Switch Function And Quantity
1 alarm
-
Body Width
1.281 inches maximum
-
Ultimate Trip Time Per Pole In Seconds
3.000 minimum all locations and 60.000 maximum all locations
-
External Actuator Linkage Arrangement
one and two linked
-
Bushing Length
0.380 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations
-
Test Data Document
81349-milc39019-4 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Trip Release Method
magnetic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Terminal Type And Quantity
4 wire hook
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Switch Contact Arrangement
single pole, double throw
-
Body Style
multipole-single actuator type