NSN: 5925-00-620-3973
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
data on certain environmental and performanc
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
0.500 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations and 5000.0 dc all locations
-
Thread Series Designator
unc
-
Reset Method
manual
-
Nominal Thread Size
0.216 inches
-
Actuator Function
trip-reset
-
Body Width
3.344 inches nominal
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Boss Height
0.125 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 ac all locations and 125.0 dc all locations
-
Thread Quantity Per Inch
24
-
Maximum Continuous Load Current Rating Per Pole
40.0 amperes ac all locations and 40.0 amperes dc all locations
-
Terminal Type And Quantity
6 quick disconnect, male
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
2.625 inches nominal
-
Body Height
3.375 inches nominal
-
Body Length
4.125 inches nominal
-
Case Material
plastic
-
Ultimate Trip Time Per Pole In Seconds
3600.000 nominal all locations
-
Test Data Document
81349-mil-c-17588 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 125 pct all locations and 100.000 maximum at 125 pct all locations
-
Inclosure Protection Type For Which Designed
shockproof and vibrationproof
-
Center To Center Distance Between Terminals Parallel To Width
1.125 inches nominal
-
Mounting Facility Type And Quantity
2 threaded stud
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
2.937 inches nominal
-
Frequency In Hertz
60.0 all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Body Style
multipole-single actuator type
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Actuator Position Designation
at pole two
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations