NSN: 5925-00-628-7782
Circuit Breakers
TRIPPER,CIRCUIT BREAKER
TRIPPER,CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Features Provided
adjustable trip release
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Adjustable Trip Setting Current Range Per Pole In Amps
+750.0/+875.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
125.0 amperes ac all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Frequency In Hertz
60.0 all locations
-
Overall Height
4.125 inches nominal
-
Unthreaded Mounting Hole Diameter
0.203 inches minimum and 0.438 inches maximum
-
Overall Length
8.438 inches nominal
-
Terminal Type And Quantity
6 screw
-
Overall Width
4.750 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
25.000 nominal at 600 pct all locations
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
105.0 all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Mounting Facility Type And Quantity
5 unthreaded hole
-
Body Style
rectangular dimensional envelope