NSN: 5925-00-629-8109
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
6.000 inches nominal
-
Body Width
4.500 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
5.593 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.500 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.594 inches nominal
-
Boss Height
0.219 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac and 250.0 dc
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Function
trip w/separate reset
-
Trip Delay Time In Seconds Per Rated Continuous Current
3600.000 nominal at 125 pct and 120.000 nominal at 200 pct
-
Frequency In Hertz
60.0
-
Terminal Type And Quantity
6 screw
-
Body Height
3.469 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
4 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac and 30.0 amperes dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac and 5000.0 dc
-
Trip Release Method
thermal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole two
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.164 inches
-
Inclosure Protection Type For Which Designed
dustproof
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal
-
Thread Series Designator
unc