Technical Characteristics
-
Unthreaded Mounting Hole Diameter
0.188 inches nominal
-
Pole Quantity
1
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac and 250.0 dc single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac and 5000.0 dc single location
-
Trip Release Characteristic
instantaneous and time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
27.000 nominal at 200 pct and 9.000 nominal at 300 pct single location
-
Inclosure Protection Type For Which Designed
general purpose
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Frequency In Hertz
60.0 single location
-
Terminal Type And Quantity
6 screw
-
Case Material
plastic
-
Mounting Facility Type And Quantity
6 unthreaded hole
-
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac and 100.0 amperes dc single location
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal-magnetic single location
-
Ultimate Trip Time Per Pole In Seconds
175.000 nominal single location
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free