NSN: 5925-00-690-5974
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 ac single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location
-
Thread Series Designator
unef
-
Overall Length
1.750 inches nominal
-
Overall Width
0.630 inches nominal
-
Frequency In Hertz
400.0 single location
-
Arc Quenching Method
magnetic blowout
-
Overall Height
2.570 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes ac single location
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Trip Release Characteristic
time delay single location
-
Manual Actuator Type And Quantity
1 toggle
-
Case Material
metal
-
Pole Quantity
1
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Circuit Protection Type
overcurrent single location
-
Thread Quantity Per Inch
32
-
Nominal Thread Size
0.375 inches
-
Reset Method
manual
-
Terminal Type And Quantity
2 wire hook
-
Trip Release Method
magnetic single location
-
Actuator Function
reset
-
~1
single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.800 maximum at 200 pct single location and 0.150 minimum at 200 pct single location and 0.010 minimum at 400 pct single location and 0.050 minimum at 300 pct single location and 0.370 maximum at 300 pct single location and 0.190 maximum at 400 pct